Transformer Dissolved Gas Analyzer | Oman 2026
video
Transformer Dissolved Gas Analyzer | Oman 2026

Transformer Dissolved Gas Analyzer | Oman 2026

Country: Oman 2026
Quantity: 2
Monitoring components: 9 gases and micro water.
Material: 316 stainless steel
Switching power supply: PT60W-220S12A512V60W

Description

 

Oman Ibri Standalone BESS Plant Project-204
Oman Ibri Standalone BESS Plant Project-205
Oman Ibri Standalone BESS Plant Project-206
Oman Ibri Standalone BESS Plant Project-207
Oman Ibri Standalone BESS Plant Project-208

 

Chromatography sees what's hidden, protecting the transformer's heart - intelligent and proactive.

General

 

Project Description

For the Duqm 500MW/2000MWh BESS project in Oman, our company supplies a transformer oil chromatography online monitoring device. Designed for extreme coastal desert conditions, it operates at -40°C to +70°C, 5% to 95% humidity, 70kPa to 110kPa, with AC240V, 50Hz, 2000W power consumption.

The device monitors nine gases (H₂, CO, CO₂, CH₄, C₂H₄, C₂H₂, C₂H₆, N₂, O₂) per IEC 60567. With IP66 and C5-M corrosion protection, it withstands high dust, water, and salt exposure.

Using high-sensitivity sensors and intelligent algorithms, it tracks dissolved gas trends, detects latent faults (partial discharge, overheating, arcing), and supports predictive maintenance. Remote data transmission enables seamless integration with the BESS monitoring system for unattended operation.

Our oil chromatography solution delivers reliable transformer health management for the Oman Duqm BESS project, enhancing power system safety and intelligence.

 

Oman Ibri Standalone BESS Plant Project-211

 

 

Technical Specification

Delivered to

Oman

Year

2026

Standard

IEC 60567

Working environment temperature

-40℃ ~ +70℃

Workplace humidity

5% to 95% (no dew formation, no ice accumulation)

Atmospheric pressure

70kPa ~ 110kPa

Working power supply

AC240V,50Hz. 1000W

Total power consumption

2000W

Monitoring component

9 gases (containing H₂, CO, CO₂, CH₄, C₂H₄, C₂H₂, C₂H₆, N₂, and O₂)

Protection level

IP66, and satisfies C5-M corrosion resistance rating.

 

Drawings

product-1462-1032

product-1378-973

 

Manufacturing

 

Electrical Control and Data Acquisition Module

product-623-745

PLC/Control Unit: Responsible for the logic control of the entire system, such as oil sample extraction, oil-gas separation, chromatographic analysis, data calculation, and alarm judgment.

Data Acquisition and Communication Module: Acquires chromatographic data and sensor signals, and uploads the results to the background monitoring system.

Power Supply Module and Terminal Block: Provides stable power to various components of the equipment and realizes signal distribution and conversion.

 

 

Oil Inlet and Outlet

Oil Inlet: The collection entrance connecting to the transformer sampling port. It draws insulating oil into the monitoring cabinet as the first step of sampling. Internal valves and filters prevent impurities and air from entering, ensuring oil sample purity.

Oil Outlet: The return outlet. After oil-gas separation and gas detection, oil samples are returned to the transformer through the outlet, forming a complete cycle.

This design enables online operation without power outages or oil loss.

product-573-1015

 

Final assembly

product-450-799

Module Installation: Install all core modules into the rack. Ensure secure mounting, leak-free seals, and correct wiring.

Oil Circuit Module: Connect the inlet and outlet oil ports to the pump and valves. Verify leak-free closed-loop circulation.

Sensors and Detectors: Connect the tower to the detectors. Shield signal cables. Install the temperature sensor and trace water sensor.

Wiring: Complete power, grounding, communication, and alarm connections using shielded cables.

Testing: Perform leak tests on the oil and gas circuits. Power on and verify one-button start, temperature stability, baseline, and alarm functions.

Sealing: Close the rack, verify the IP protection rating, and affix the nameplate.

 

Testing

 

No.

Inspection Items

Inspection Contents

Measurement Standards

Conclusions

1

Measurement Error Testing

Multi-components(H2,CH4,C2H2,C2H6,C2H4,CO,Co2)

The lowest detection limit for measurement error or ±30%, whichever is greater.

PASS

2

Measurement Repeatability Testing

For total hydrocarbons≥50pL/L in the same oil sample, perform six consecutive gas analyses in oil with measurement repeatability expressed as the relative standard deviation (RSD) OF total hydrocarbons results.

RSD of total hydrocarbons measurement results ≤5%

PASS

3

Minimum Detection Cycle Testing

Under normal operating conditions, the time required by the device from automatic sampling to providing analysis results.

The minimum monitoring cycle should not exceed 2 hours.

PASS

4

Insulation Resistance Testing

Insulation Resistance

Under normal testing atmospheric conditions, measured with a 500V insulation resistance meter, the insulation resistance between each independent circuit and exposed conductive parts, and between the independent circuits themselves, should be ≥5MΩ

PASS

5

Dielectric Strength Testing

Dielectric Strength

Under normal testing atmospheric conditions, each independent circuit and the exposed conductive parts, as well as between the independent circuits, should withstand a 2KV power frequency withstand test at 50Hz for 1 minute without breakdown flashover and component damage.

PASS

6

Continuous Power-On Testing

The

The device operates within its effective measuring range, continuously powered for 72 hours. During continuous power-on, the data recording interval should not exceed 2 hours, or there should be at least 12 recordings every 24 hours.

Over the 72-hour period, all functions of the device operate normally, data can be normally uploaded, measurement trends are continuous and stable, with no abnormal fluctuations.

PASS

 

Oman Ibri Standalone BESS Plant Project-5458
Oman Ibri Standalone BESS Plant Project-5459

 

Packing and Shipping

 

Packing

 

Oman Ibri Standalone BESS Plant Project-5498
Oman Ibri Standalone BESS Plant Project-5503

 

Shipping

 

Oman Ibri Standalone BESS Plant Project-5518

Oman Ibri Standalone BESS Plant Project-5520

 

Site and Summary

 

In conclusion, the transformer oil chromatography online monitoring device for Oman's Duqm 500MW/2000MWh BESS project delivers robust, internationally compliant performance in one of the region's most demanding grid-scale energy storage applications. Designed for coastal desert conditions, it operates at -40°C to +70°C with IP66 and C5-M protection against dust, water, and salt spray.

The device monitors nine dissolved gases per IEC 60567, enabling early detection of partial discharge, overheating, and arcing faults to support predictive maintenance. As the BESS serves as the "core stabilizer" of Oman's 400kV grid, our solution provides reliable transformer health management, seamless integration, and unattended operation capability, enhancing power system safety and intelligence for the Middle East region.

product-700-934

 

Hot Tags: transformer dissolved gas analyzer | oman 2026, China transformer dissolved gas analyzer | oman 2026 manufacturers, suppliers, factory, dga analysis for transformer condition monitoring, winding hot spot temperature monitoring, Transformer Core Grounding Current Monitor, Online Partial Discharge Monitoring System for Transformer, dissolved gas analyzer for transformer oil, Transformer Dissolved Gas Analyzer